APPLICATIONS:
Aircraft Cargo Operations – Containers
Electrical Cabinets
Renewable Energy (Wind Turbines)
Buses / Trains / Boats
Storage Cabinets
Manufacturing Warehouses
Intermodal Shipping
Plant Rooms
Power Stations
Mechanical / Electrical Control Rooms
Drones
Commercial / Military Aircraft Applications
DESCRIPTION: The AAE FPS Appliance is an “Autonomous” Fire Protection System Appliance that provides smoke detection and fire suppression for containers, rooms, cabinets, stations, or compartments that are not monitored. The Appliance is not mechanically or electrically connected to, or dependent on, any other system. The Appliance detects smoke and discharges an aerosol agent that completely floods the containment area. The amount of aerosol can be sized to fit any compartment. The Appliance can send signals to a separate monitoring station. The Appliance can receive signals from other sequential FPS systems. It is made of a rugged construction and has a long service life.
OPERATION: The FPS Appliance is equipped with two “Single Channel” smoke detectors. One detector provides the “A” loop; and the other detector provides the “B” loop. Each detector features one bi-colored LED for indication of status. In a normal standby condition, the LED flashes “Green” every 3 seconds. When the detector senses that its sensitivity has drifted outside the UL listed sensitivity window, the LED will “flash Red” every 3 seconds. When the detector senses smoke and goes into alarm, the status LED “latches solid on RED”. An alarm is indicated when “both” detector channels sense smoke. When an alarm is indicated by the detectors, a signal is sent to the FPS Appliance’s Control Panel. The Control Panel immediately (less than 5 seconds) discharges each of its aerosol containers. The total amount of aerosol agent completely floods the area to be protected.
SPECIFICATIONS:
Classes of Fire (NFPA 2010) …………………………………………Class A, Class B, Class C
Power Requirements …………………………12-volt Lithium Ion Phosphate Battery
Dimensions ………………………………………………………………………………. 27” x 19” x 5.5”
Appliance Weight ………………………………………………………………34.0 (+/- .10) pounds
Self-activation temperature of Aerosol Generating Solid Compound……300oC
Environmental parameters
- Ozone Depletion Potential……………………………………………………………………..Zero
- Global Warming Potential……………………………………………………………………..Zero
- Atmospheric Life Time………………………………………………………………….Negligible
Aerosol discharge time………………………………seconds (Min.) – 10 seconds (Max.)
Transportation Classification
- Class 9
- UN Identification: 3335 (Air) & 3077 (Ocean)
- Packaging Group: PGIII
- Shipping Guidelines for maximum weight: Ground-None, Ocean-None, Cargo Air-400kg (881 lbs., Passenger Air-30kg (66lbs)
Testing has shown conclusively that:
- The AAE FPS Appliance’s smoke detectors will respond “within 60 seconds of initiation of a small amount of smoke as described in U.S. FAA Advisory Circulars AC 25-9A and in AC 25-22, Paragraph 39 (§25.858)”.
- Discharge of the aerosol from the Appliance’s extinguishers occurs in less 5 seconds after detection.
- Discharge of the aerosol from the Appliance’s extinguishers will completely flood the containment area within 60 seconds.
- Discharge of the aerosol from the Appliance’s extinguishers will not cause structural damage to surrounding structures.
- The AAE FPS Appliance’s Suppression System will perform it’s intended function on “a realistic fire threat under realistic environmental conditions”.